A whole water utility on one SCADA
A fictional city: every screen is a simulation running in your browser. Pick a site on the left or
click it on the map. ×
The demo needs JavaScript.
SPS-14 Sewage pumping station
Simulation
i What we automate here
08:00:00
No alarms
Mimic of a wastewater pumping station: inlet sewer, wet well with three pumps, discharge valves, rising main and emergency overflow
Inlet sewer
Inflow
40 l/s
LT 01
1.62 m
HH
LL
Rising main
to treatment works
PT 01
1.20 bar
FT 01
0.0 l/s
Emergency overflow
to watercourse
EDM-01 · overflow
Not spilling
0 events · 0 min today
M
V1
P1
STOPPED
0.0 A
AUTO
M
V2
P2
STOPPED
0.0 A
AUTO
M
V3
P3
STOPPED
0.0 A
AUTO
STATION
Duty pump P1
Pumps running 0 of 3
Pumps available 3 of 3
Power 0.0 kW
Energy per m³ –
Pumped today 0 m³
Energy today 0.0 kWh
Control Level, auto
Telemetry OK
Duty rotation Each cycle
Swipe sideways to see the whole screen.
Station P1 P2 P3
Simulation not a real site
Inflow 40 l/s
Start a storm
Speed ×1 ×10 ×30
Restart this screen
Pump P1 Stopped
Current 0.0 A Run hours 1,834.2 h Starts 0 Valve V1 Open
Auto Manual Off
Start Stop Close valve
Simulate Ragging Reset
Pump P2 Stopped
Current 0.0 A Run hours 1,790.6 h Starts 0 Valve V2 Open
Auto Manual Off
Start Stop Close valve
Simulate Ragging Reset
Pump P3 Stopped
Current 0.0 A Run hours 1,812.9 h Starts 0 Valve V3 Open
Auto Manual Off
Start Stop Close valve
Simulate Ragging Reset
Alarms 0 active · 0 unacknowledged
Acknowledge all
No alarms
Trend · last 15 min
Level, 0–4 m
Inflow, 0–150 l/s
Outflow, 0–150 l/s
What we deliver
For any site in this demo: a complete ICA software package, built offline from your scope and
your client's standards. Your engineer reviews and accepts it; your team does the site work, SAT and
commissioning. We never need access to live systems.
Functional design specification The control philosophy for the site, each requirement traced to a test.
I/O schedule Signals, ranges, alarms and interlocks in one controlled list.
PLC and SCADA code Control logic and screens like the ones in this demo, to your client's standard.
FAT pack, pre-run on an emulator Test scripts run against simulated I/O before your FAT.
More about us: how we work , the team ,
data and analytics .
×
About this demo
The demo city
A fictional city at the scale of a large capital: about nine million people, roughly 2,000 Ml/d into supply with about a fifth lost to leakage, river intakes and raw water reservoirs, three treatment works and a desalination plant, a ring main in a tunnel, district meter areas, four sewage works and an interceptor tunnel behind the storm overflows.
Each site on the map opens its own screen: the kind of screens we build for real sites, here with a simulation behind them.
Scenarios on the overview show the whole system at work: a storm, a burst main, a dry summer, a heatwave.
Alarms and events, the historian and the reports collect data from every screen.
The screen style at the top switches every screen: dark, high-performance (ISA-101) or classic, and the running colour.
Typical signals
Supply and demand Leakage Sewage flows Overflow spills Tunnel level Grid import
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Tell us about your next site
×
What we automate here
River intakes and raw water storage
Abstraction from the river into raw water reservoirs that hold weeks of supply, and the pumping that moves it on to treatment.
Intake screens, raw water pumps and reservoir inlets, on level and within the abstraction licence.
Abstraction cut back automatically when the river falls to its hands-off flow.
River quality monitors that close the intake on a pollution alert, so the works draws on the reservoir.
Reservoir levels, transfers and draw-off to the treatment works.
Typical signals
River level and flow Abstraction flow Turbidity and ammonia Screen differential level Pump run, trip, current Reservoir level
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Have an intake or reservoir scheme? Tell us
×
What we automate here
Water treatment works
Large works that filter and disinfect river water: rapid gravity filters, ozone and activated carbon, chlorination and treated water pumping. Our lead engineer led his department's work on a filtration plant upgrade of about 4,700 signals (case study ).
Filter level control, headloss and turbidity on every filter.
Automatic backwash with queueing: drain-down, air scour, water wash, return to service.
Ozone and chlorine dosing paced on flow and trimmed on quality.
Contact tank, treated water storage and high-lift pumps into supply.
Typical signals
Raw and filtered turbidity Filter level and headloss Backwash step Ozone dose Free chlorine Treated water level
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Upgrading a treatment works? Tell us
×
What we automate here
Ring main, boosters and service reservoirs
Trunk mains, a deep tunnel ring main with shaft pumping stations, and service reservoirs on high ground that balance supply and demand through the day.
Shaft and booster pumps on variable-speed drives, controlled on pressure or flow.
Service reservoir filling on level, moved to cheaper night-time electricity where storage allows.
Duty rotation, standby take-over and gentle starts and stops against surge.
Low-pressure and reservoir high- and low-level alarms.
Typical signals
Suction and delivery pressure Drive speed and current Reservoir level Inlet valve position Flow and totals
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Have a booster or reservoir scheme? Tell us
×
What we automate here
Distribution network: pressure, leakage, consumption
Thousands of kilometres of mains, split into district meter areas (DMAs), each with a metered inlet, pressure management and loggers at critical points.
DMA inlet flow and minimum night flow against leakage targets.
Burst detection from flow and pressure, with alarms to the control room.
Pressure-reducing valves controlled by time of day or by flow.
Consumption from bulk and smart meters into the historian and reports.
Typical signals
DMA inlet flow Critical point pressure PRV inlet and outlet pressure Minimum night flow Logger battery and signal
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Planning network monitoring? Tell us
×
What we automate here
Sewage pumping stations
Hundreds of wet-well stations with two or three submersible pumps lift sewage from low-lying catchments into the trunk sewers.
Duty, assist and standby control on wet-well level, with duty rotation and staggered starts.
Standby take-over when a pump trips; motor current, run hours and starts for each pump.
High-level and emergency overflow alarms, with spill monitoring.
Discharge valve interlocks, low-level protection and back-up floats.
Telemetry to the control centre: status, alarms, flows and energy.
Typical signals
Wet-well level High-high and low-low floats Pump run, trip, auto Motor current
Discharge valve open / closed Rising main flow Delivery pressure Overflow spill (EDM)
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Have pumping stations to automate? Tell us
×
What we automate here
Storm overflows and storm tanks
Combined sewer overflows along the river, storm tanks, and an interceptor tunnel that stores storm sewage until the works can treat it. Every spill has to be monitored and reported.
Event duration monitoring (EDM): spill start, stop and duration from level or flow at the weir.
Storm tank and tunnel filling, draining and return pumping to the works.
Pass-forward flow control, so that the works takes all it can before a spill.
Screen and penstock status and control.
Spill records with data gaps flagged, ready for your client's reporting.
Typical signals
Weir level Storm tank level Spill flag and duration Pass-forward flow Return pump run, trip Screen status Penstock position
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Have a storm overflow scheme coming up? Tell us
×
What we automate here
Sewage treatment works
Large activated sludge works serving millions of people, with sludge digestion that turns biogas into electricity.
Inlet works: screens, grit removal and flow to full treatment, with storm tanks.
Aeration on dissolved oxygen and ammonia, with blower duty and air pressure.
Sludge pumping, digestion, gas holders and combined heat and power (CHP) engines.
Final effluent quality against the permit.
Typical signals
Inlet flow Screen differential level Dissolved oxygen Air flow and pressure Final effluent ammonia Biogas and CHP output
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Have a works upgrade coming up? Tell us
×
What we automate here
Energy metering
Pumping and treatment use a lot of electricity. Metering every site and every large drive shows where it goes and what can move to cheaper hours.
Power and energy meters on incomers, motor control centres and large drives.
Energy per megalitre for each site and pump, against a baseline.
Own generation from CHP and solar, grid import and export.
Peak-time warnings and pumping schedules that avoid the most expensive hours.
Typical signals
kW and kWh per incomer Power factor Drive power CHP output Tariff band
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Want to see where the energy goes? Tell us
×
What we automate here
Telemetry and control centre
The link between hundreds of remote sites and the control room. The city overview at the top of this page is the control-room view; this screen shows the communications behind it. Our lead engineer built telemetry for 53 sewage pumping stations.
Outstations on radio, 4G and IP links, polled or reporting by exception.
Link health for every site, and data kept at the outstation while a link is down.
Alarms routed to the right people, by priority and shift.
Central SCADA, historian and reports for every site.
Typical signals
Site communication status Signal strength Last poll Alarms and events Logged data
Every package: FDS, I/O schedule, PLC and SCADA code, and a FAT pack run on an emulator.
What we deliver
Extending telemetry? Tell us
×
Legend
Colours and symbols
Shown in the screen style you have chosen; switch the style or the running colour and this legend changes with it.
Equipment
Running : pump, blower or engine in service
Stopped : available, ready to start
Tripped : stopped by a fault, needs a reset
Off : switched out of service by the operator
Valve open
Valve closed
Valve moving (blinks while it travels)
Flow : moving dashes in a pipe (no animation in the high-performance style)
Alarms
1 Priority 1 : act now. Blinking until acknowledged.
2 Priority 2 : act soon. Steady once acknowledged.
3 Priority 3 : for information. A returned alarm stays in the list, greyed, until acknowledged.
Dots in the menu : the most serious alarm on that site or group; green when there are none.
Liquids
Clean water
Raw water
Sewage
Sludge
Chemical dosing
Measurements
FT 01 55 l/s Instrument and its live value: LT level, FT flow, PT pressure, AT analyser
Screen styles
Dark : a modern control-room screen with live flow animation.High-performance : grey screens where colour
means something is abnormal, and nothing moves (the ISA-101 approach many control rooms now use).Classic : bright 3D
equipment and green-on-black readouts, as on many systems still in service.
Running: green or red : standards differ. Some show running equipment in green and stopped in red; others, common in
UK utilities, show running (energised) in red and stopped in green. On a real project the screens follow your client's HMI
standard.